Particle and Aerosol Research
Vol. 12, No. 1, March 2016, Pages 11-20
|
ISSN : 1738-8716 (Print)
ISSN : 2287-8130 (Online)
|
Performance Characteristics of Louver Dust Collectors
Sang-Hee Woo1),2), Jong Bum Kim1), Tong-Il Park1), Se-Jin Yook2), Soon Bark Kwon3), and Gwi-Nam Bae1),*
1)Center for Environment, Health and Welfare Research, Korea Institate of Science and Technology, Seoul, Korea
2)School of Mechanical Engineering, Hanyang University, Seoul, Korea
3)Transportation Environmental Research Team, Korea Railway Research Institute, Uiwang, Korea
*Corresponding author.
Tel.: +82-2-958-5676, E-mail: gnbae@kist.re.kr
Received 16 November 2015, Revised 27 January 2016, Accepted 12 February 2016, Available online 31 March 2016
http://dx.doi.org/10.11629/jpaar.2016.12.1.011
Abstracts
A large amount of wear dust generated during train operation is a major dust source in urban railway tunnels. To check possibility of a louver dust collector for the removal of dust in the railway tunnel, five louver dust collector models were designed and their performance was tested in a wind tunnel. JIS Z 8901 Class 8 dust was used as a test dust. Pressure drop and particle collection efficiency were evaluated with the face velocity ranging from 1 m/s to 4 m/s. At this low velocity range, particle collection efficiency of the louver dust collector was found to be insensitive to air velocity and design parameters. Pressure drop was under 40 Pa, and PM10 and PM2.5 collection efficiencies were approximately 50% and 30%, respectively.
Keywords
Dust collector, Louver, Particle collection efficiency, Pressure drop, Urban railway